About this item
| Type | Value |
|---|---|
| Voltage Range | 12 to 690V AC/DC |
| Nominal Voltage | 12/24/50/120/230/400/690V AC (16 to 400Hz), DC (±) |
| Tolerance | Light on at more than: |
| (Threshold Voltage) | 7±3V (12V LED) 18±3V (24V LED) 37.5±4V (50V LED) 75%±5% of nominal voltage (120/230/400/690V LED) |
| Response Time | <0.6s at 100% of each nominal voltage |
| Peak Current | ls<3.5mA (at 690V) |
| Measurement Duty | 30s ON (operation time) 240s OFF (recovery time) |
| Voltage Range | 100 to 690V AC (50/60Hz) |
| System | Three-phase 4-wire system 200 to 690V phase-to-phase AC (50/60Hz) |
| Phase Range | 120±5 degree |
| Detection Range | 0 to 400kΩ+50% |
| Test Current | Approx. 1.5μA (battery 3V, 0Ω) |
| Applicable standards | IEC 61243-3, IEC 61010-1, IEC 61557-7 CAT Ⅳ 600V / CAT Ⅲ 690V Pollution degree 2, IEC 60529 (IP65) |
| Operating temperature and humidity range | -15 to 55°C, relative humidity 85% or less (no condensation) |
| Storage temperature and humidity range | -20 to 70°C, relative humidity 85% or less (no condensation) |
| Power source | LR03 (AAA) 1.5V×2 |
| Dimension | 246(L)×64(W)×26(D) mm |
| Weight | Approx. 190g (including batteries) |
| Accessories | LR03 (AAA) 1.5V×2 KTA01 (4mm metal tips [2pcs/set]) KTA02 (4mm rubber caps [2pcs/set]) Instruction manual |