Kyoritsu 3122b The Kyoritsu KEW 3122B is a battery‑powered, analogue high‑voltage insulation resistance tester designed for field and shop use. Its robust, ergonomic housing and built‑in hard case protect the instrument and leads during transport, while the analogue pointer and colour‑coded scales provide immediate visual feedback on insulation condition. Auto‑ranging between low and high resistance scales (0–5 GΩ / 2–200 GΩ) allows the tester to maintain full output voltage (5 kV ± 5%) down to 0.2 GΩ, ensuring accurate readings even on partially deteriorated insulation. Bright LEDs indicate which range is active, complementing the analogue display for rapid judgment in bright or low‑light environments. Weighing approximately 1.7 kg (including eight C‑cell batteries) and rated to CAT III 600 V / CAT IV 300 V, the KEW 3122B delivers up to 40 hours of continuous use. Its safety‑compliant design (IEC 61010‑1, ‑2‑030; IEC 61010‑031) and optional recorder adaptor make it ideal for maintenance of cables, transformers, generators, and switchgear.

Total price 33,450.00 EG

Product Features

  • Complies with IEC 61010‑1, ‑2‑030 (CAT III 600 V/CAT IV 300 V) and IEC 61010‑031 safety standards.
  • Dual, automatic resistance scales (0–5 GΩ / 2–200 GΩ) with colour‑coded LEDs.
  • Maintains rated output (5 kV ± 5%) down to 0.2 GΩ for accurate low‑level readings.
  • Analogue pointer for intuitive trend monitoring.
  • Audible high‑voltage warning buzzer.
  • Includes water‑resistant hard carrying case.
  • Optional MODEL 8324 recorder adaptor available.

Product Applications

  • Industrial installations maintenance.
  • Cable insulation testing.
  • Transformer insulation testing.
  • Generator insulation testing.
  • Switchgear insulation testing.

Specifications

TypeValue
Operating TimeApprox. 40 hours (100 MΩ load at 5000 V range)
Power Source8 × LR14 (C‑cell) alkaline batteries
Weight≈ 1.7 kg (including batteries)
Dimensions 177 × 226 × 100 mm
Output CharacteristicsMaintains full 5 kV output down to 0.2 GΩ
Safety CategoryCAT III 600 V / CAT IV 300 V
Accuracy (Outside First Range)± 10% of indicated value or 0.5% of scale length
Accuracy (First Range)± 5% of indicated value (0.2 – 100 GΩ)
Measuring Ranges0 – 5 GΩ / 2 – 200 GΩ (auto‑ranging)
Test VoltageDC 5000 V ± 5%